JSK-X-JLA34

3-Phase Earthing Device

Ref. SS 428 91 01, EN 61230

Line clamp JSK is for connection directly to busbars when contact fittings are not available. Insulating poles MGV, MDV/MSV and operating socket JGS are used to operate the line clamps.The line clamps conducting parts are made of hot pressed electrolytic copper. The loop is made of hardened AlSi-alloy and has a contact plate of hardened, surface treated steel. The thread has a Heli-Coil insert in stainless steel.
Other steel components are made of stainless steel. The line clamps have stainless steel spring washers to ensure constant contact pressure. The earthing cable, made of highly flexible ESTPR-insulated copper strands, has sealed cable connections, which prevent humidity from penetrating the cable. The earthing cable is connected by compression to the earthing device.
Cable shoe JLA 34 and connecting cluster JFG 4 (rubber insulated) are made of hot pressed electrolytic copper and the hand bolt is made of stainless steel.
JLA is for connection to stationary earthing fittings JVF and JBF.

JSK-X-JLA34

excl. earthing cable

E-nr:

No E-number available

Earthing device excl. earthing cable

E-No.
Type
Line Clamp
Cable shoe/
Earth Clamp
Earthing cable area
mm2
Rated Current
max. kA/1s
Weight kg/unit
JSK-JLA34 JSK
JLA 34
25 – 120
27,0
5,3*

* Incl. cable connection for max earthing cable area.

Pls. specify earthing cable area and earthing cable length when ordering.

 

Earthing Cables for Earthing- and Short-circuiting devices

Type
Earthing Cable area

mm2
Rated
current
kA/1s
Weight
kg/m
ESTPR25 

25
5,7
0,3
ESTPR35 35
8,0
0,4
ESTPR50
50
11,5
0,5
ESTPR70 70
16,0
0,7
ESTPR95 95
21,0
1,0
ESTPR120 120
27,0
1,2
ESTPR150 150
34,0
1,5
ESTPR185 185
42,5
1,9