Operating Pole MTV150-K4 / MTV150-K5

Ref. SS 428 91 05, SS 428 91 10, EN 61230, EN 61235, EN 61243-1
For indoor and outdoor use.
Operating pole MTV-K is used as an insulating pole when earthing and voltage detection are performed. The connector fitting at the poles working end accepts accessories such as operating sockets, torque tools, disconnection hooks, fuse holders and voltage detectors. The pole is fitted with a hand guard that marks where the handgrip section ends and the insulating section starts. This hand guard must not be exceeded when in use. The inner tube must always be extended to its full length when working with this pole. The top tube is sealed to prevent humidity penetrating. The overall length can be infinitely adjusted using the hand grip section.
The insulating pole is made of yellow, fiberglass reinforced polyvinyl ester and has an outside diameter of 55 mm (MTV 150-K5) or 51 mm (MTV 150-K4). The connector fitting is made of nylon. The lower end is fitted with a protective cap made of rubber. This pole is also suitable for use with branch and tree cutting tools etc.
Extension sections MSV are available as required. These sections are fitted to the top fitting of the operating pole.

Operating Pole MTV150-K4 / MTV150-K5

E-No.
Type
Operating
Voltage
max kV
Carrying Length
mm
Length
Total
mm
Insulating
Section
mm
Hand Grip

Section
mm
Weight
kg/unit
E1652945 MTV 150-K4 36 1500 4600 1200 1300-3300 3,0
E1652930 MTV 150-K5 36 1500 5600 1200 1300-4300 3,7

Earthing Cables for Earthing- and Short-circuiting devices

Type
Earthing Cable area

mm2
Rated
current
kA/1s
Weight
kg/m
ESTPR25 

25
5,7
0,3
ESTPR35 35
8,0
0,4
ESTPR50
50
11,5
0,5
ESTPR70 70
16,0
0,7
ESTPR95 95
21,0
1,0
ESTPR120 120
27,0
1,2
ESTPR150 150
34,0
1,5
ESTPR185 185
42,5
1,9